Technical Data
VSD\VCD – Recommended Heater settings & sizing for a 15 °C Heat Rise @ 30% Open*
| Pa | 20 | 30 | 40 | 50 | 60 | 70 |
|---|
| Heating Element | Heating Element | Heating Element | Heating Element | Heating Element | Heating Element |
|---|
| Neck Size (mm) | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set |
|---|
| 150 | 0.75 | 0.35 | 47% | 0.75 | 0.34 | 45% | 0.75 | 0.50 | 67% | 0.75 | 0.50 | 67% | 0.75 | 0.60 | 80% | 0.75 | 0.65 | 87% |
| 200 | 1.25 | 0.60 | 48% | 1.25 | 0.70 | 56% | 1.25 | 0.75 | 60% | 1.25 | 0.90 | 72% | 1.25 | 1.00 | 80% | 1.25 | 1.00 | 80% |
| 250 | 1.50 | 0.85 | 57% | 1.50 | 1.00 | 67% | 1.50 | 1.15 | 77% | 1.50 | 1.30 | 87% | 1.50 | 1.40 | 93% | 1.50 | 1.50 | 100% |
| 300 | 2.00 | 1.00 | 50% | 2.00 | 1.25 | 63% | 2.00 | 1.50 | 75% | 2.00 | 1.65 | 83% | 2.00 | 1.75 | 88% | 2.00 | 2.00 | 100% |
| 350 | 2.50 | 1.30 | 52% | 2.50 | 1.50 | 60% | 2.50 | 1.85 | 74% | 2.50 | 1.85 | 74% | 2.50 | 2.25 | 90% | 2.50 | 2.50 | 100% |
VSW – Recommended Heater settings & sizing for a 15 °C Heat Rise @ 30% Open*
| Pa | 30 | 40 | 50 | 60 | 70 |
|---|
| Heating Element | Heating Element | Heating Element | Heating Element | Heating Element |
|---|
| Neck Size (mm) | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set |
|---|
| 150 | 0.75 | 0.35 | 47% | 0.75 | 0.40 | 53% | 0.75 | 0.45 | 60% | 0.75 | 0.50 | 67% | 0.75 | 0.55 | 73% |
| 200 | 1.25 | 0.60 | 48% | 1.25 | 0.70 | 56% | 1.25 | 0.80 | 64% | 1.25 | 0.85 | 68% | 1.25 | 0.90 | 72% |
| 250 | 1.50 | 0.75 | 50% | 1.50 | 1.00 | 67% | 1.50 | 1.10 | 73% | 1.50 | 1.20 | 80% | 1.50 | 1.30 | 87% |
| 300 | 2.00 | 1.00 | 50% | 2.00 | 1.20 | 60% | 2.00 | 1.35 | 68% | 2.00 | 1.50 | 75% | 2.00 | 1.60 | 80% |
VLN1, 2 Slot, Pattern C – Recommended Heater settings & sizing for a 15 °C Heat Rise @ 30% Open*
| Pa | 30 | 40 | 50 | 60 | 70 |
|---|
| Heating Element | Heating Element | Heating Element | Heating Element | Heating Element |
|---|
| Length (mm) | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set | Total kW | kW Setpoint | Set |
|---|
| 600 | 0.75 | 0.30 | 40% | 0.75 | 0.35 | 47% | 0.75 | 0.35 | 47% | 0.75 | 0.4 | 53% | 0.75 | 0.45 | 60% |
| 900 | 1.25 | 0.45 | 36% | 1.25 | 0.55 | 44% | 1.25 | 0.60 | 48% | 1.25 | 0.7 | 52% | 1.25 | 0.70 | 56% |
| 1200 | 1.50 | 0.65 | 43% | 1.50 | 0.75 | 50% | 1.50 | 0.80 | 53% | 1.50 | 0.9 | 60% | 1.50 | 1.00 | 67% |
| 1500 | 2.00 | 0.85 | 43% | 2.00 | 1.00 | 50% | 2.00 | 1.10 | 55% | 2.00 | 1.2 | 60% | 2.00 | 1.30 | 65% |
*To limit stratification in heating Rickard recommends that the heater outputs be limited to the values published in the tables above. The calculated values will ensure that the heat rise is no more than 15°C in VAV diffusers. Please note that these values are a guide and are calculated at 30% volume for VAV diffusers. By adjusting the diffuser damper position down, a smaller volume will create a larger heat rise and therefore increase the likelihood of stratification.
Total kW column - Indicates the maximum fitted heater size recommended
kW Setpoint column - Indicates the maximum heater setting recommended to achieve a 15°C (VAV) heat rise
Set column - Is the MLM Heater Output % value required to achieve a 15°C (VAV) heat rise.